First Device profile
1.1 device overview
SAI3880D series digital generator protection device with high performance chip supports universal hardware platform, easy to maintain; the Ethernet communication, high-speed data transmission and reliable. Complete localization of Chinese display technology, simple operation.
Based on waterproof, dust, anti vibration design, can be run in a variety of field conditions.
Suitable for capacity of 50MW and below the fire and hydro generator protection.
1.2 main features of the device
An Motorola 32 bit microcontroller technology, the stability and speed of products is guaranteed
The protection. The 14 bit a / D converter, optional measurement module dedicated to the A / D conversion accuracy is up to 24 bits and the measurement indicators easily reach
The purpose of configuration with high capacity RAM and Flash Memory, can record 8 to 50 recorded reports, record the number of events is not less than 1000
An independent tuning of 32 sets of protection setting value, safe and convenient switch
In high precision clock chip, and equipped with GPS hardware circuit for the whole time, system clock synchronization
It is equipped with high speed Ethernet communication interface, and the integration of IEC870-5-103 standard communication protocol
In the electrical design with the machine, no adjustable device
In high grade, quality assurance component selection
An excellent anti-interference performance, panel or installed in the switch cabinet without other anti-jamming module
The purpose of self diagnosis function perfect
The chassis design of waterproof and dustproof and anti vibration.
The purpose of debugging conceptual design
1.3 function configurationFunction configuration of SAI3880D digital generator differential protection deviceDifferential quick break, ratio brake differential, CT disconnection locking differential, CT disconnection alarm, stator overvoltage protection, stator ground fault protection, overload alarm, anti time overcurrent protectionFunction configuration of backup protection device for SAI3881D digital generatorTransverse differential protection, loss of excitation protection, rotor one point grounding protection, rotor two points grounding protection composite voltage over current protection, inverse time negative sequence overcurrent protection, Pt disconnection alarm, non electricity protection (generator water shutoff, and the generator thermal, generator excitation accident, main steam valve closed),
Function configuration of SAI928digital measurement and control device
AC measurement
A group of three-phase current, three-phase voltage and zero sequence voltage, power, frequency, power, power factor
Switch input
11 way switch input, can be the whole set of non electric power for "trip" or "alarm", the first 4 non electricity can be arbitrarily set trip exit
Switch output
8 way switch contact output, the 4 switch jump closing control
control loop
Jump control circuit, circuit breaker hand jump, hand closing operation and hop position indication
低周減載
利用這一元件,可以實現分散式的頻率控制,當系統頻率低于整定頻率時,此元件就能自動判定是否切除負荷。
低頻減載功能邏輯中設有一個滑差閉鎖元件以區分故障情況、電機反充電和真正的有功缺額。
考慮低頻減載功能只在穩態時作用,故取AB相間電壓進行計算,試驗時仍需加三相平衡電壓。當此電壓(UAB)低于閉鎖頻率計算電壓時,低周減載元件將自動退出。
說明:現場試驗條件不具備時,該試驗可免做。模擬量正確,則精度由軟件**。
2.10 低壓解列
適用于發電廠和系統間的聯絡線保護,可以實現低壓控制,當系統電壓低于整定電壓時,此元件就能自動判定是否切除負荷。
低壓解列的判據為:
1)三相平衡電壓,U相<UDY
2)dV/dt<V/T
3)T>Tudy
4)負序線電壓<5V
5)本發電機有載(負荷電流>0.1In)
本功能通過控制字實現投退,PT斷線時閉鎖低壓保護。
2.11 過負荷元件
過負荷元件監視三相的電流,其動作條件為:
1)MAX(IF)>Ifh
2)T>Tgfhgj:告警
3)T>Tgfhtz:跳閘
其中Ifh為過負荷電流定值。
本功能通過壓板實現投退,過負荷告警與跳閘的選擇由控制字選定。
2.12 過電壓保護
過壓監視三相的電壓,其動作條件為:
1)MAX(UF)>Ufh
2)T>Tgytz:跳閘
其中Ufh為過壓定值。
2.13 逆功率保護
過負荷元件監視三相的電流,其動作條件為:
1)MAX(PF)>Pfh
2)T>Tngltz:跳閘
其中Pfh為逆功率定值。
2.14 PT斷線檢測
在下面三個條件之一得到滿足的時候,裝置報發“PT斷線”信息并點亮告警燈:
1)三相電壓均小于8V,某相(a或c相)電流大于0.25A,判為三相失壓。
2)三相電壓和大于8V,較小線電壓小于16V,判為兩相或單相PT斷線。
3)三相電壓和大于8V,較大線電壓與較小線電壓差大于16V,判為兩相或單相PT斷線。
裝置在檢測到PT斷線后,可根據控制字選擇,或者退出帶方向元件、電壓元件的各段保護,或者退出方向、電壓元件。PT斷線檢測功能可以通過控制字(KG1.15)投退。
2.15 小電流接地選線
小電流接地選跳系統由SAI-3884D裝置和NZ8000監控主站構成。當系統發生接地時,3U0抬高。當裝置感受到自產3U0有突變且大于10V,即記錄當前的3U0,3I0。與此同時,母線開口三角電壓監視點向主站報送接地信號。主站則在接到接地信號后調取各裝置內記錄的3U0,3I0量,計算后給出接地點策略。
無主站系統時,單裝置接地試跳判據為:合位時3U0大于18V,試跳分位后3U0小于18V,即判為本發電機接地。
2.16 數據記錄
本裝置具備故障錄波功能。可記錄的模擬量為Ia、Ib、Ic、3I0、Ua、Ub、Uc、Ux、Ii0,可記錄的狀態量為斷路器位置、保護跳閘合閘命令。所有數據記錄信息數據存入FLASH RAM中,可被PC機讀取。可記錄的錄波報告為8個以上,每次錄波數據總時間容量為1S,分兩段記錄,動態捕捉并調整記錄時間。可記錄的事件不少于1000次。本裝置除記錄系統擾動數據外,還記錄裝置的操作事件、狀態輸入量變位事件、更改定值事件及裝置告警事件等。
2.15 遙信、遙測、遙控功能
遙控功能主要有三種:正常遙控跳閘操作和合閘操作,接地選線遙控跳閘操作。
遙測量主要有:IAc、(IBc)、ICc、UA、UB、UC、UAB、UBC、UCA、COS¢、P、Q、F 和電度。所有這些量都在當地實時計算,實時累加,三相有功無功的計算消除了由于系統電壓不對稱而產生的誤差,且計算完全不依賴于網絡,精度達到 0.5 級。
遙信量主要有:16 路遙信開入、裝置變位遙信及事故遙信,并作事件順序記錄,遙信分辨率小于2ms。
主要從事:110KV及以下變電站綜合自動化系統、發電廠綜合自動化系統、水電站綜合自動化系統、調度綜合自動化系統、工業控制自動化系統、高壓諧波治理系統、微機五防系統、電力自動化智能儀表、微機消諧系統、智能開關電源直流系統、消諧消弧及過壓保護裝置等研究、生產、銷售和服務。公司的不斷開發研制適合不同用戶要求的各種系列、各種規格電氣自動化產品、努力追求、力爭做國內**業性價比較優產品。
公司始終把“以人為本,以德為先”作為事業發展基石,強調員工和企業利益一致,公司匯聚了一批電力系統及自動化、計算機應用、自動控制和通信技術,諧波治理等各類專業的科技精英。高學歷、高素質、專業化的人才隊伍使科技成果迅速轉化成現實的生產力。力求打造國內*自動化*。
公司始終堅持“質量*一”的方針,質量控制貫穿于從研發到生產過程的每一個環節,確保生產全過程處于受控狀態。嚴格的產品檢測制度,完善的測試手段,良好的產品售前、中、后服務。公司嚴格按照ISO9001的質量技術認證要求,先后榮獲:中國電力自動化**企業、質量信譽、服務AAA企業、中國著名品牌、質量服務****單位等。
服務中國電力,打造世界品牌,深圳國網南瑞憑借自身實力已服務在全國的各類行業,部分有:陜西送變電工程、珠海湛江35KV變電站、鞍鋼鋼鐵、上海寶鋼、河南王杭莊煤礦、山西同煤潞安煤礦、山西沁新選煤、神華煤礦、遼陽水泥、洛鉬集團、江西雙張化工、貴州水城、河南義馬礦、西電東送、京福高速、遵義供電局、南方電網、三峽工程等大型重點工程項目。